Siemens LMV51 Series Basic Documentation page 283

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
19.11 Commissioning the O
19.11.1 Setting ratio control
First, adjust the ratio curves as with the LMV51... system. The excess
O2 rate must be selected high enough, ensuring that, irrespective of
ambient conditions (combustion chamber and fuel pressure, temperature
and pressure of the combustion air), the O2 level will not fall below the O2
setpoint of O2 trim control.
Parameterize the loads at the curvepoints proportional to the effective fuel rate (amount
of fuel). For that purpose, ascertain the load with the help of the fuel counter.
The curvepoint identifies the smallest load where O2 trim control is still possible. In nor-
mal situations, this is the low-fire position. Point 1 defines the curve for reducing the air
rate below point 2. If, in the low-fire position, no further air reduction is possible (e.g. be-
cause the air damper has already fully closed), curvepoint 1 must be selected as the low-
fire point. In that case, O2 trim control will only be performed up to curvepoint 2.
The O
ratio value between the curvepoints should be linear. When O
2
activated, precontrol will transfer any nonlinearity to the actual O
ing the load, the actual O
the O
progression by approaching the loads between the curvepoints. If the O
2
value has such nonlinearities, they can be corrected by setting intermediate curve-
points.
The more thoroughly the ratio curve is set, the easier the subsequent adjustment of O2
trim control, and the more accurate O2 trim control will be.
If the ratio curves are changed later, the O2 trim controller must also be
readjusted.
19.11.2 Setting the O
Next, the O
monitor must be adjusted. When making the adjustment for the first time,
2
the O
monitor should remain deactivated to avoid undesired responses. When chang-
2
ing settings later, it can stay activated.
Set the O2 min. value as low as possible to ensure a high level of availability. The O2
min. value marks the boundary between the permanently non-harzardous range and
the potentially hazardous range.
Above or at the O
nently occur.
Guide values (for Europe): CO = 2,000 ppm, soot number 3.
The values vary, depending on the type of plant. They need to be checked.
After setting all O
min. values, the O
2
The setting can be made in 2 different ways.
Basic Documentation LMV5...
19 Addendum 4: LMV52... with O2 trim control and O2 module
2
value fluctuates about the O2 setpoint. Check the linearity of
2
2
monitor
min. value, hazardous conditions must not perma-
2
monitor can be activated.
2
trim control system
trim control is
2
value. When adjust-
2
ratio
2
283/301
CC1P7550en
13.08.2004