Application Example; Implementation; Technical Data, Flame Supervision; Qri (Suited For Continuous Operation) - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Application example

Implementation

Technical data,
flame supervision
QRI (suited for
continuous operation)

Connection diagram

Siemens Building Technologies
HVAC Products
The parameters offer the following setting choices:
Single-detector operation (corresponding to the LMV51..., plus error message
if 2 flame detectors are connected)
QRI_B or ION (parallel operation of QRI... / QRB... and ION, flame signal if 1 of
the 2 channels indicates a flame)
QRI_B and not ION (parallel operation of QRI... / QRB... and ION, flame signal
if only the QRI... / QRB... indicates a flame)
QRI_B (parallel operation of QRI... / QRB... and ION, flame signal if the QRI... /
QRB... indicates a flame; ION will not be evaluated)
ION and not QRI_B (parallel operation of QRI... / QRB... and ION, flame signal
if only ION indicates a flame)
ION (parallel operation of QRI... / QRB... and ION, flame signal if ION indicates
a flame; the QRI... / QRB... will not be evaluated)
QRI_B and ION (both must indicate a flame; this selection is not available with
the «Extraneous light» block)
Selective supervision of pilot ignition with ION, which means that the ION probe only
detects the pilot flame. The main flame is supervised with the QRI...
Parameter «Extraneous light» must be set to «QRI_B | ION», which means that extra-
neous light is detected if 1 of the 2 flame detectors indicates that a flame is present.
Parameter «Pilot phase» must be set to «ION», which means that in the pilot phases
(Phases 40 through 50), only ION will be evaluated.
Parameter «Operating phase» must be set to «QRI_B &/ ION», which means that in the
operating phases (Phases 52 through 62) only the QRI... may deliver a flame signal.
With this kind of parameterization, a flame signal via ION in the operating phases will
lead to loss of flame.
Note: All measured voltages refer to connection terminal N (X10–02, terminal 4).
Supply voltage operation / test at terminal POWER QRI...
(X10–02, terminal 2)
Minimum signal voltage required at terminal FSV / QRI...
(X10–02, terminal 6)
SIEMENS
Landis & Staefa
QRI
Made in Germany
For detailed information, refer to Data Sheet N7719.
Basic Documentation LMV5...
4 Burner control
black
brown
7719a01E/0502
approx. DC 14 / 21 V
display flame approx. 50 %
LMV...
X10-02 / 6
blue
X10-02 / 4
X10-02 / 2
+
0...10 V
Ri > 10 MΩ
DC 3.5 V
35/301
CC1P7550en
13.08.2004