Siemens LMV51 Series Basic Documentation page 236

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A6
69
LC
A6
6A
LC
A6
6B
LC
A6
6C
LC
A6
6D
LC
A6
6E
LC
A6
6F
LC
A6
70
LC
A6
71
LC
A6
72
LC
A6
73
LC
A6
74
LC
A6
75
LC
A6
76
LC
A6
77
LC
A6
78
LC
A6
79
LC
236/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Load Controller
Fault internal A/D converter
Internal Fault Load Controller
Fault during PWM test
Internal Fault Load Controller
Faulty reference voltage
Internal Fault Load Controller
Fault transmitter power supply
Internal Fault Load Controller
Fault analog output, voltage deviation too
great
Internal Fault Load Controller
Fault during resistance test PT100 input
(X60)
Internal Fault Load Controller
Fault during diode test PT100 input
External Fault Load Controller
Measured value varies too much:
PT100 sensor (X60)
External Fault Load Controller
Measured value varies too much:
PT100 line (X60)
External Fault Load Controller
Measured value varies too much:
PT1000 (X60)
External Fault Load Controller
Measured value varies too much:
PWM
External Fault Load Controller
Measured value varies too much:
Voltage measurement input 2 (X61)
External Fault Load Controller
Measured value varies too much:
Current measurement input 2 (X61)
External Fault Load Controller
Measured value varies too much:
Voltage measurement input 3 (X62)
External Fault Load Controller
Measured value varies too much:
Current measurement input 3 (X62)
External Fault Load Controller
Excessive voltage value or wrong polarity
PT100 sensor (X60)
External Fault Load Controller
Excessive voltage value or wrong polarity
PT100 line (X60)
Meaning for the LMV5x system
Troubleshooting
*1)
*1)
*1)
*1)
*1)
*1)
*1)
Check wiring of input.
Check wiring of input.
Check wiring of input.
*1)
Check wiring of input. Check input voltage value for hum-
ming voltages
Check wiring of input. Check input voltage value for hum-
ming voltages
Check wiring of input. Check input voltage value for hum-
ming voltages
Check wiring of input. Check input voltage value for hum-
ming voltages
Check wiring of input
Check wiring of input