Siemens LMV51 Series Basic Documentation page 276

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

276/301
Siemens Building Technologies
HVAC Products
19.7 Auxiliary functions
19.7.1
Warning when flue gas temperature is too high
If a flue gas temperature sensor is connected and activated, a warning is delivered in
case the adjusted flue gas temperature is exceeded. Excessive flue gas temperatures
are an indicator of increased boiler losses ⇒ boiler should be cleaned. The warning
threshold for gas- and oil-firing can be set separately.
Parameter:
MaxTempFlueGas Gas
Parameter:
MaxTempFlueGas Oil
19.7.2
Combustion efficiency
If an O
sensor, a combustion air and flue gas temperature sensor is connected and
2
activated, the combustion efficiency will be calculated and displayed.
Parameter:
Combustion air temperature sensor (NoSensor, Pt1000,
LG-Ni1000)
Parameter:
Flue gas temperature sensor (NoSensor, Pt1000, LG-Ni1000)
To ensure that the calculation will be made correctly, the fuel parameters must be se-
lected and set in accordance with the type of fuel burnt.
Also refer to section 19.10.2 Parameterization
The calculation is made according to the following formula (1. BimSchV = 1. Bundes-
Imissionsschutzverordnung = First Federal Imission Protection Decree):
Flue gas volume ratio:
O2 value dry:
Flue gas losses:
Efficiency:
Basic Documentation LMV5...
19 Addendum 4: LMV52... with O2 trim control and O2 module
V_afNmin
AVft =
V_atrNmin
AVft O2ContentAir
O2_tr =
O2ContentAir
O2Value_Wet
A2
=
⎜ ⎜
qa
O
2
ContentAir
η
=
100
%
qa
F
+ AVft - 1
(
ϑ
+
• ⎟ ⎟
B
flue
gas
O
2
_
tr
)
ϑ
su
pply
air
CC1P7550en
13.08.2004