Siemens LMV51 Series Basic Documentation page 184

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Description of the connection terminals (cont'd)
Connection symbol
X10-01
X10-02
X10-03
X50
X51
X52
184/301
Siemens Building Technologies
HVAC Products
terminals (AC 120 V)
Description
PIN4
x
Neutral conductor (N)
PIN3
x
Power signal transformer
PIN2
x
AC power signal GO
PIN1
x
AC power signal G
PIN6
x
QRI... (IR detector) signal voltage
PIN5
x
Protective earth (PE)
PIN4
x
Neutral conductor (N)
PIN3
x
Power signal
PIN2
x
QRI... (IR detector) power supply
PIN1
x
QRB... signal voltage
PIN1
x
Ionization probe
PIN6
x
Reference ground (PELV)
PIN5
x
Communication signal (CANL)
PIN4
x
Communication signal (CANH)
PIN3
x
AC power supply for actuators / display
and operating unit AZL...
PIN2
x
PIN1
x
Shield connection (functional earth)
PIN6
x
Reference ground (PELV)
PIN5
x
Communication signal (CANL)
PIN4
x
Communication signal (CANH)
PIN3
x
AC power supply for actuators / display
and operating unit AZL...
PIN2
x
PIN1
x
Shield connection (functional earth)
PIN4
x
Functional earth
PIN3
x
AC power supply from transformer to
LMV51... system
PIN2
x
Reference ground (PELV)
PIN1
x
AC power supply from transformer to
LMV51... system
Basic Documentation LMV5...
10 Description of the connection
13.08.2004
Electrical rating
AC 120 V +10 % / -15 %, 50...60 Hz,
max 1 mA
AC 12 V +10 % / -15 %, 50...60 Hz,
max 1.2 mA
Umax DC 5 V
AC 120 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
DC 14 / 21 VC
Imax 100 mA
max. DC 8 V
Umax (X3-04-PINS)
Imax. 0.5 mA
DC U ← 5 V, Rw = 120 Ω ,
level to ISO-DIS 11898
AC 12 V +10 % / -15 %,
50...60 Hz,
fuse max. 4 A
DC U ← 5 V, Rw = 120 Ω ,
level to ISO-DIS 11898
AC 12 V +10 % / -15 %, 50...60 Hz,
fuse max. 4 A
AC 12 V +10 % / -15 %, 50...60 Hz
AC 12 V +10 % / -15 %, 50...60 Hz
CC1P7550en