Siemens LMV51 Series Basic Documentation page 248

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
C5
04
ABE
C5
08
SA
C5
10
VSD module Version Conflict
C5
20
O2
D1
#
VSD module Fault Feedback VSD Module
D1
01
VSD module Fault Feedback VSD Module
D1
02
VSD module Fault Feedback VSD Module
D1
03
VSD module Fault Feedback VSD Module
D3
#
O2
01
D3
O2
02
D3
O2
03
D3
O2
E1
---
VSD module Fault Feedback VSD Module
248/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Version Conflict
Software of the AZL5... too old
Version Conflict
Software of 1 or several actuators too old Replace actuator
Software of VSD module too old
Version Conflict
Software of O2 module too old
Basic unit has detected a wrong state of
the VSD module. Corresponds to the "8x"-
faults with the other CAN users
CRC error
Key error main loop counter
No feedback for max. number
Fault Feedback O2 Module
Basic unit has detected a wrong stage of
the O2 module
Fault Feedback O2 Module
CRC error
Fault Feedback O2 Module
Key error main loop counter
Fault Feedback O2 Module
No feedback for max. number
Basic unit has detected a ROM-CRC fault
in the VSD module when checking its
feedback signal
Meaning for the LMV5x system
Troubleshooting
Replace AZL5... or update its software
Replace basic unit
Replace O2 module
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace defective module
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective module
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective module
CC1P7550en