2-Position Controller (C = On / Off); Diagram; Cold Start Thermal Shock Protection (Cstp); Description - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

2-position controller
(C = ON / OFF)
Menu level 1
Params & Display

Diagram

Cold start thermal shock
protection (CSTP)

Description

168/301
Siemens Building Technologies
HVAC Products
Example: Modulating control
After the boiler setpoint in °C has been entered, the switch-on and switch-off point of
the 2-position controller in % will be given.
The switching points will be calculated in relation to the current setpoint.
Setpoint:
Example:
SD_ModOn
SD_ModOff
Controller loop open (Off)
Controller loop closed (On)
Menu level 2
Menu level 3
LoadController
ControllerParam
SD_ModOff
W
SD_ModOn
R=ON
Y=OPEN
Y=CLOSED
When the cold start thermal protection has been activated, a boiler – after having dropped
below a predefined switch-on threshold – will be heated up in multistage operation.
This approach ensures that when cold, the boiler does not have to satisfy the maximum
demand for heat within a very short period of time. Thermal strain on the boiler will thus
be prevented.
The cold start sequence will be activated when, on startup, the actual value lies below
the switch-on threshold. When cold start thermal shock protection is activated, the ma-
nipulated variable - on cold start - will be increased in a stepwise fashion using the ad-
justed output step (or the next stage will be switched on).
Start output for the cold start is the minimum load. The increase of the output by the
output step depends on 2 criteria:
1. If the predefined change of the actual value is not reached with the current output
(setpoint step modulating or setpoint step multistage), the output will be increased
by this step (output step) when the maximum time has elapsed.
2. If the predefined change of the actual value is reached with the current output within
the maximum time, the output will be increased by one output step.
When the switch-off threshold is reached, the cold start sequence will be terminated
and normal control operation started.
Basic Documentation LMV5...
8 Commissioning instructions for the LMV5... system
70 °C
+5 % ( = 3.5 K)
+10 % ( = 7 K)
70 + 3.5 = 73.5 °C
70 - 7 = 63 °C
Menu level 4
SD_ModOn
SD_ModOff
Setpoint
Actual value
Menu level 5
Menu level 6
7550f07E/0502
CC1P7550en
13.08.2004