Siemens LMV51 Series Basic Documentation page 208

Burner control with integrated fuel / air ratio control and load control, load control including o2 trim control for forced draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
10
08
BU
10
09
BU
10
0A
BU
10
0B
BU
10
0C
BU
10
0D
BU
10
0E
BU
10
0F
BU
10
10
BU
10
11
BU
10
12
BU
10
13
BU
10
14
BU
10
15
BU
10
16
BU
10
17
BU
10
18
BU
10
19
BU
10
1A
BU
10
1B
BU
11
01
BU
15
#
SA
VSD module
15
01..3F
SA
208/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Internal Fault Basic Unit
Pressure switch valve proving
Internal Fault Basic Unit
Safety valve oil feedback
Internal Fault Basic Unit
Fuel valve 1 oil feedback
Internal Fault Basic Unit
Fuel valve 2 oil feedback
Internal Fault Basic Unit
Fuel valve 3 oil feedback
Internal Fault Basic Unit
Safety valve gas feedback
Internal Fault Basic Unit
Fuel valve 1 gas feedback
Internal Fault Basic Unit
Fuel valve 2 gas feedback
Internal Fault Basic Unit
Fuel valve 3 gas feedback
Internal Fault Basic Unit
Safety chain burner flange
Internal Fault Basic Unit
Safety relay feedback
Internal Fault Basic Unit
Pressure switch gas minimum
Internal Fault Basic Unit
Pressure switch gas maximum
Internal Fault Basic Unit
Ignition transformer feedback
Internal Fault Basic Unit
Fan pressure switch
Internal Fault Basic Unit
Start release oil
Internal Fault Basic Unit
Heavy oil direct start
Internal Fault Basic Unit
Load controller open
Internal Fault Basic Unit
Load controller closed
Internal Fault Basic Unit
Start release gas
Internal Fault Basic Unit
Basic unit has detected a short-circuit in
the contact feedback network
Fault Positioning Actuator
Basic unit has detected a positioning er-
or
ror on 1 / several actuators (incl. the VSD
Fan Speed not reached
module)
Fault Positioning Actuator
The diagnostic value is made up of the
following faults or their combinations (the
individual diagnostic codes are added up
in hexadecimal format)
Meaning for the LMV5x system
Troubleshooting
*1)
Check if actuator is overloaded.
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the relevant actuators (re-
fer to diagnostic code).