Error
Diagnostic
Device
code
code
03
84
SA
85
#
SA
01
85
SA
02
85
SA
03
85
SA
86
#
LC
01
86
LC
02
86
LC
03
86
LC
87
#
ABE
01
87
ABE
02
87
ABE
226/301
Siemens Building Technologies
Basic Documentation LMV5...
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
Display
Fault Feedback Aux Actuator 1
No feedback for max. number
Fault Feedback Aux Actuator 2
Basic unit has detected wrong state of
the auxiliary actuator
Fault Feedback Aux Actuator 2
CRC error
Fault Feedback Aux Actuator 2
Key error main loop counter
Fault Feedback Aux Actuator 2
No feedback for max. number
Fault Feedback Load Controller
Basic unit has detected wrong state of
the internal load controller
Fault Feedback Load Controller
CRC error
Fault Feedback Load Controller
Key error main loop counter
Fault Feedback Load Controller
No feedback for max. number
Fault Feedback AZL
Basic unit has detected wrong state of
the AZL...
Fault Feedback AZL5...
CRC error
Fault Feedback AZL5...
Key error main loop counter
Meaning for the LMV5x system
Troubleshooting
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
*1)
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace the faulty ABE
CC1P7550en
13.08.2004