Installation
4.2.2
EMC
4.2.3
4.2.4
4.2.5
GB - 20
Connection of the Control
In order to prevent a malfunction caused by interference voltage supply on the
control inputs, the following directions should be observed:
- Use shielded/drilled cables
- Lay shield on one side of the inverter onto earth potential
- Lay control and power cable separately (about 10...20 cm apart)
- Lay crossings in a right angle (in case it cannot be prevented)
Digital inputs
Internal voltage supply
4
5
11 12 13 14
Analog inputs
Internal analog set-point setting
7
8
9
PE
R = 3...10 kΩ
Outouts
30 V DC/1 A
1
2
3
9 10
When using inductive consumers at the relay output a protective wiring (i.e. free
wheeling diode) is necessary to protect the relay!
External voltage supply
4
5
PE
13...30 V DC
External analog set-point setting
8
9
+
-
SPS
PE
Analog output:
+
0...10VDC / max. 5mA at
Ri ≥ 56 KΩ const.
0...1mADC at
Ri ≤ 5 kΩ const.
6
12 13 14
PE
+
PE
0...±10 V DC
Ri = 40 kΩ