Special Adjustments - KEB COMBIVERT M4 Instruction Manual

Table of Contents

Advertisement

Available languages

Available languages

5.6
Max. ramp current
Max. constant
current

Special Adjustments

The following parameters serve to optimize the drive and adaption onto certain
applications. These adjustments can be ignored at the initial startup.
This function protects the frequency inverter against switching off by overcurrent
during the acceleration ramp. When the ramp reaches the adjusted value here,
then it is stopped so long until the current decreases again. CP.2 displays "LAS"
at active function.
Adjustment range:
Resolution:
Factory setting:
Customer adjustment:
This function protects the frequency inverter against switching off due to
overcurrent during constant output frequency. When exceeding the adjusted
value here, the output frequency is reduced until the value drops below the
adjusted value. CP. 2 displays "SSL" at active function.
Adjustment range:
Resolution:
Factory Setting:
Customer adjustment:
C.14
C.15
on
off
on
off
f
real
f
set
Operating of the unit
10...200 %, 200%=oFF up to case D
10...200%; >150% = oFF from case E
1 %
140 %
_______ %
10...200 %, 200%=oFF up to case D
10...200%; >150% = oFF from case E
1 %
200 %
_______ %
t
LAD-stop
t
Current limit
t
t
GB - 27

Advertisement

Chapters

Table of Contents
loading

Table of Contents