Technical Data; Device Data; Rated Voltages; Connection Type - WAGO 750 XTR Manual

End module with potential group xtr i/o module for terminating the fieldbus node; with potential group; extreme
Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

WAGO I/O System 750 XTR
750-600/040-001 End Module with Potential Group XTR
3.6

Technical Data

3.6.1

Device Data

Table 5: Technical Data – Device
Width
Depth (from upper edge of DIN-rail)
Height
Weight
Degree of protection
3.6.2

Rated Voltages

Table 6: Technical Data – Rated Voltages
Supply voltage (system)
Voltage (potential group)
Current carrying capacity
(CAGE CLAMP
Pollution degree
Isolation to adjacent I/O modules and
system/field
Rated surge voltage (system/field)
3.6.3

Connection Type

Table 7: Technical Data – Field Wiring
Connection technology: inputs/outputs
Conductor cross-section
Strip length
Table 8: Technical Data – Data Contacts
Data contacts
3.6.4

Mechanical Conditions

Table 9: Technical Data – Mechanical Conditions
Vibration resistance
*
Follow the installation instructions
-connectors)
®
Rated voltage U
nominal
Insulation type Reinforced insulation
Overvoltage category III up to 3,000 m above sea level;
Device Description
12 mm
60.6 mm
100 mm
48 g
IP20
5 VDC; via data contacts
0 ... 230 VAC/DC; power supply
via CAGE CLAMP
connectors
®
10 A
2 per EN60664-1
AC 300 V per EN/UL 61010-2-201
II up to 5,000 m above sea level
5 kV (EN 60870-2-1 / class VW3),
or 6.4 kV (EN6 1010-1)
8 × CAGE CLAMP
®
0.25 ... 2.5 mm², AWG 24 ... 14
8 ... 9 mm / 0.33 in
Slide contact, hard gold plated, self-
cleaning
Max. 5g
*
19
Manual
Version 1.0.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-600/040-001

Table of Contents