Jump Frequency 1 Bandwidth; Jump Frequency 2 Bandwidth - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F271

Jump Frequency 1 Bandwidth

Program ⇒ Special ⇒ Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #1 (see
F270).
Jump Frequency 2
Program ⇒ Special ⇒ Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at F273). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.

Jump Frequency 2 Bandwidth

Program ⇒ Special ⇒ Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #2
(F272).
Jump Frequency 3
Program ⇒ Special ⇒ Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at F275).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Jump Frequency 3 Bandwidth
Program ⇒ Special ⇒ Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(F274).
Preset Speed 8
Program ⇒ Frequency ⇒ Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
H9 ASD Installation and Operation Manual
F018
for more information on
Direct Access Number — F271
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Direct Access Number — F272
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F273
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F287
131