6.4.10 Replacing a Water Inlet or Outlet Temperature Sensor

Prerequisites
Context
Temperature sensor can be replaced with power on.
Recommended tools: needle-nose pliers.
Preparation: maintain from the rear door.
Procedure
Step 1 Open the rear door and remove the air filters.
Step 2 Cut off the cable ties and the thermal insulation form on the pipe where the temperature
sensor is secured.
Step 3 Remove the water inlet or outlet temperature sensor probe.
Figure 6-13 Position of water inlet and outlet temperature sensors
(1) Water inlet temperature sensor
Issue 09 (2020-01-10)
The water inlet or outlet temperature sensor needs to be replaced.
A spare and functional temperature sensor is available.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
(2) Water outlet temperature sensor