NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Parameter
Rotation
Rotation period
Rotation time
Forced rotation
Requirement
control
Issue 09 (2020-01-10)
Description
value ranges from 1 to
Total number of units.
Disable or enable the
active and standby
smart cooling products
to change identity after
a certain time,
maximizing their
service life.
Rotation days (1–30).
24 hours in a day
(0–23).
Forced rotation
specifies whether to
enable a forcible
rotation on the group
before the specified
rotation time. After a
forced rotation, the
accumulated time is
recalculated.
Enable or disable the
requirement control for
the master device.
When the
requirement control
is Enable, the
master device
synchronizes data
(the temperature and
humidity control
type and set points
of the master device
and other
parameters) to the
slave device, and all
the smart cooling
products in the
group refer to the
mode delivered by
the master device.
When the
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
be active units by the
device number,
beginning with the
address 1 until to
Number of running
units. The rest will
become the standby
ones.
This function is
recommended when
the heat is even.
7 by default.
0 by default.
This item is set to No
by default. If forced
rotation is required,
the function is set to
Yes.
The requirement
control function is
recommended for the
following scenario: In
one teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same,
and device heat loads
are distributed evenly.
4 ACC Introduction
Default Value
Disable
7 day(s)
0
No
Disable
95