NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Procedure
Step 1 Tap Alarms > Query Act. Alarms > CW valve abnormal feedback on the home screen.
The alarm information is displayed, as shown in
Figure 4-49 Manually clearing the alarm
Step 2 Tap Clear, a dialog box for confirming clearance is displayed.
Step 3 Tap Yes, the Command triggered successfully. message is displayed.
Step 4 Tap OK.
----End
4.5.7 How to Enable a Humidity and Temperature Sensor
Context
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Step 2 Set Cold-aisle sensor 1 and Cold-aisle sensor 2 to Enable, as shown in
Issue 09 (2020-01-10)
A humidity and temperature sensor needs to be enabled after it is installed in an aisle.
To enable a sensor, log in as the Admin or Engineer user.
This section describes how to enable Cold-aisle sensor 1 and Cold-aisle sensor 2.
Copyright © Huawei Technologies Co., Ltd.
Figure
4-49.
4 ACC Introduction
Figure
4-50.
123