Setting Communications Parameters (Modbus Settings) - Huawei NetCol5000-C Series User Manual

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Figure 4-7 IP settings
Step 2 Set the parameters by referring to
Table 4-3 IP address settings
Parameter
IP assigning
mode
IP address
Subnet mask
Gateway
----End

4.3.2.5 Setting Communications Parameters (Modbus Settings)

Context
You can set parameters for Modbus RTU and Modbus TCP on the Modbus setting screen.
Figure 4-8
Issue 09 (2020-01-10)
Setting Method
Set according to the actual plan.
Set according to the actual plan.
Set according to the actual plan.
Set according to the actual plan.
To set communications parameters, log in as the Admin or Engineer user.
If Connection mode is set to Server, a smart cooling product can be accessed by a
maximum of one element management system (EMS) clients at the same time. If
Connection mode is set to Client, a smart cooling product can be connected only to the
EMS with the corresponding IP address. If Connection mode is set to Server+client, a
smart cooling product can be accessed by a maximum of one EMS clients and connect to
the EMS with the corresponding IP address at the same time.
shows the screen for setting the Modbus communications parameters.
Copyright © Huawei Technologies Co., Ltd.
Table
4-3.
4 ACC Introduction
86