Huawei NetCol5000-C Series User Manual page 164

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Alarm
Alarm Name
ID
a109
Cold-aisle
1/2/3 humid
invalid
a110
Cold-aisle
1/2/3 T/H brd
comm failed
a111
Hot-aisle
1/2/3 temp
invalid
a112
Hot-aisle
1/2/3 humid
invalid
a113
Hot-aisle
1/2/3 T/H brd
comm failed
a114
iCooling
Issue 09 (2020-01-10)
Severity
System
Operation
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
2. The T/H sensor is
faulty.
1. Dirt or water exists
around the T/H
sensor, which
leads to a detection
fault.
2. The T/H sensor is
faulty.
1. The cables to the
T/H sensor are
loose or damaged.
2. The DIP switch of
the T/H sensor is
set incorrectly.
3. The T/H sensor is
faulty.
4. The
communication
port of the control
board is faulty.
1. Dirt or water exists
around the T/H
sensor, which
leads to a detection
fault.
2. The T/H sensor is
faulty.
1. Dirt or water exists
around the T/H
sensor, which
leads to a detection
fault.
2. The T/H sensor is
faulty.
1. The cables to the
T/H sensor are
loose or damaged.
2. The DIP switch of
the T/H sensor is
set incorrectly.
3. The T/H sensor is
faulty.
4. The
communication
port of the control
board is faulty.
1. There is no A/C
Recovery Measures
1. Remove dirt or
water from the T/H
sensor.
2. Maintain or replace
the T/H sensor.
1. Check the cables to
the T/H sensor.
2. Set the DIP switch
of the T/H sensor
correctly by
referring
3.14.5
(Optional) Installing
a T/H
Sensor.
3. Maintain or replace
the T/H sensor.
4. Maintain or replace
the control board.
1. Remove dirt or
water from the T/H
sensor.
2. Maintain or replace
the T/H sensor.
1. Remove dirt or
water from the T/H
sensor.
2. Maintain or replace
the T/H sensor.
1. Check the cables to
the T/H sensor.
2. Set the DIP switch
of the T/H sensor
correctly by
referring
3.14.5
(Optional) Installing
a T/H
Sensor.
3. Maintain or replace
the T/H sensor.
4. Maintain or replace
the control board.
1. Ensure a A/C master
155