Setting Communications Parameters (Ip Settings) - Huawei NetCol5000-C Series User Manual

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Parameter
Supply-air temp
set point,
Supply-air humid
set point
Return-air temp
set point,
Return-air humid
set point
Cold-aisle temp
set point,
Cold-aisle humid
set point
Hot-aisle temp
set point,
Hot-aisle humid
set point
Cold aisle sensor
1, 2, 3
Hot aisle sensor
1, 2, 3
----End

4.3.2.4 Setting Communications Parameters (IP Settings)

Context
To set communications parameters, log in as the Admin, or Engineer user.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > IP Settings.
displayed.
Issue 09 (2020-01-10)
Description
on the Average,
Maximum, or
Minimum of the
temperatures
collected by each
sensor.
Sets the required
humidity and
temperature in a room
or aisle.
Sets the sensors in
cold aisles to Enable.
Sets the sensors in hot
aisles to Enable.
Copyright © Huawei Technologies Co., Ltd.
Configuration Principle
collector.
Maximum: Select Maximum if the
temperature is to be controlled based on
the maximum data value collected by the
collector.
Minimum: Select Minimum if the
temperature is to be controlled based on
the minimum data value collected by the
collector.
The ACC controls the temperature and
humidity based on the set value. For example,
if Temp control type is set to Return-air,
Return-air temp set point is set to 30.0, and
Return-air humid set point is set to 25.0, the
ACC will control the temperature and
humidity around the return-air vent of the
smart cooling product to a temperature of
30° C and humidity of 25% RH.
Enable the corresponding humidity and
temperature sensor installed in the cold aisle.
Enable the corresponding humidity and
temperature sensor installed in the hot aisle.
4 ACC Introduction
Figure 4-7
is
85

Advertisement

Table of Contents
loading

Table of Contents