3.11.2 Connecting Condensate Drainpipes

3.11.2.1 (Optional) Connecting the Water Pump Drainpipe

Context
This section applies only to models with water pump.
Procedure
Step 1 Unfasten the water pump drainpipe and pull it out of the hole at the bottom (or the top) of the
cabinet.
Issue 09 (2020-01-10)
Connect the water pump drainpipe in the top drainage scenario. Determine whether to
connect the automatic condensate drainpipe depending on the actual situation.
Connect the automatic condensate drainpipe and water pump drainpipe (if a water pump is
used) in the bottom drainage scenario.
Do not over bend the drainpipe when securing the drainpipe. Use the thermal insulation
pipe to wrap the water pump drainpipe.
Check that hoses at two ends of the water pump and hose to the three-way connector
T-junction valve are securely installed.
If a drainage port exists onsite, the automatic drainpipe can be connected to that port.
In the cabinet, fasten the pipe to vertical pillar of rear door with cable ties.