4.3.3 Commissioning Guide

4.3.3.1 Entering Diagnostic Mode

Context
Procedure
Step 1 Choose Maint > Diagnostic Mode > Enter > Yes.
Figure 4-21 Entering the diagnostic mode
Issue 09 (2020-01-10)
On the diagnostic mode screen, you can turn on or off components, and control their
output ratio.
If you need to manually turn on or off system components in diagnostic mode, log in as
the Admin or Engineer user. Ensure that the smart cooling product is started before
operation.
The screen for entering the diagnostic mode:
Components are interlocked. Therefore, buttons for turning on or off certain components are in gray,
indicating that operations of the components are not allowed.
Copyright © Huawei Technologies Co., Ltd.
4 ACC Introduction
Figure 4-21
is displayed.