NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Procedure
Step 1 Hold the manual adjustment button and manually turn the chilled water valve to the maximum
scale (100%).
Figure 3-32 Adjusting the chilled water valve
Step 2 Connect a pressure gauge, reducing valve, and nitrogen cylinder to any one of the needle
valves. Inject 0.8 MPa (when the pressure is stable) nitrogen, and leave them for 24 hours.