Huawei NetCol5000-C Series User Manual page 163

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Alarm
Alarm Name
ID
a099
Return-water
temp invalid
a101
CW valve 1/2
abnormal
feedback
a102
Indoor fan
1/2/3/4/5/6/7/8
overspeed
a103
Indoor fan
power alarm
a104
In-cabinet
water
overflow
a105
Indoor fan
failure
a106
In-cabinet
water sensor
fault
a108
Cold-aisle
1/2/3 temp
invalid
Issue 09 (2020-01-10)
Severity
System
Operation
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated, and
the indoor fan
output is less
than 85%.
Critical
The alarm is
generated, and
the
NetCol5000-C
shuts down.
Critical
The alarm is
generated.
Major
The alarm is
generated, and
the
NetCol5000-C
shuts down.
Major
The alarm is
generated.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
3. The supply water
temp displayed is
different from the
actual temp.
1. The cables to the
temperature sensor
are loose or
damaged.
2. The temperature
sensor is faulty.
1. The cables to the
CW valve are
loose or damaged.
2. The CW valve is
faulty.
1. The cables to the
indoor fan are
loose or damaged.
2. The indoor fan is
faulty.
1. The power module
of the indoor fan is
faulty.
2. The cables to the
power module of
the indoor fan are
loose or damaged.
1. Water exists in the
overflow pan.
2. The cabinet
overflow sensor is
disconnected.
1. The indoor fan is
faulty.
2. The cables to the
indoor fan are
loose or damaged.
The cabinet overflow
sensor is faulty.
1. Dirt or water exists
around the T/H
sensor, which
leads to a detection
fault.
Recovery Measures
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
1. Adjust the cables to
the CW valve.
2. Maintain or replace
the CW valve.
1. Check the cables to
the indoor fan.
2. Maintain or replace
the indoor fan.
1. Maintain or replace
the power module.
2. Check the cables to
the dry contact of
the power module.
1. Check and clear the
water.
2. Maintain or replace
the cabinet overflow
sensor.
1. Maintain or replace
the indoor fan.
2. Check the cables to
the indoor fan.
Maintain or replace the
cabinet overflow sensor.
1. Remove dirt or
water from the T/H
sensor.
2. Maintain or replace
the T/H sensor.
154