4.3.2.7 Setting Teamwork Control Parameters

Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
smart cooling products as follows:
Context
Procedure
Step 1 On the home screen, tap
Issue 09 (2020-01-10)
To use the teamwork iCooling mode, upgrade the software to V100R001C60 or
V100R002C00 first.
In the teamwork iCooling mode, each micro module supports only one teamwork network,
and all smart cooling products must be networked in the teamwork mode. Smart cooling
products managed by different micro modules cannot be networked in teamwork mode.
Smart cooling products managed by each micro module must be connected to the NMS
separately.
L0/L1 linkage is supported only when all micro modules corresponding to the same chiller
work in iCooling mode.
In a water chilling system with a chilled water tank, the chilling station teamwork control
system must provide the following functions: During the chilled water storage process, the
chiller produces chilled water at the water storage temperature, and the water storage logic
takes priority over the iCooling control logic. After the chilled water storage process is
complete, the chiller controls the temperature of chilled water as instructed by the iCooling.
If the system does not have this function, contact Huawei technical support.
If the software versions of all smart cooling products in the group are ACC V100R001C60
or V100R002C00, unit addresses can be set to integers ranging from 1 to 32, and can be
inconsecutive. The teamwork control page displays units currently online.
If the software versions some smart cooling products in the group are ACC V100R001C60
or V100R002C00 and that of others are versions earlier than ACC V100R001C60, unit
addresses must be set to consecutive integers; otherwise, the teamwork control page
displays an exception.
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork control number for them. At most four teamwork control groups
can be assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the same group
cannot be the same (address range: 1–32). The smart cooling product addressed 1 is the
master one that collects, processes, and delivers data. It is recommended that you set the
unit address numbers from one to the Total number of units in this group.
The parameters in this section are for reference only. Set actually parameter values as
required.
To change teamwork settings, log in as the Admin or Engineer user.
Copyright © Huawei Technologies Co., Ltd.
> Teamwork Settings.