Lmv5 Will Not Modulate Properly - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
 
1. Ensure that the LMV5 is in automatic mode through the following menu path: 
 
 
ManualOperation > Autom/Manual/Off = Automatic 
 
2. Check the PID settings and make sure that they are set for the application. 
 
P‐Part – This is the proportional band.  The proportional band increases firing rate based on 
how  far  below  setpoint  the  temperature  /  pressure  is.    Smaller  values  cause  a  more 
aggressive response to a drop in pressure / temperature relative to setpoint.  Values that 
are too small will cause hunting.  Typical setting:  10% to 30%. 
 
I‐Part – This is the integral part, which serves to eliminate steady state "droop" caused by 
the  proportional  band  setting.    Thus,  this  works  hand  in  hand  with  P‐Part  to  bring  the 
pressure / temperature up to setpoint.  Smaller values cause a more aggressive response (a 
setting  of  1  is  most  aggressive).    Values  that  are  too  small  will  cause  overshoot.    Typical 
setting:    80  sec  to  300  sec.    A  setting  of  0  deactivates  the  feature,  but  this  is  not 
recommended. 
 
D‐Part – This is the derivative part, which serves to eliminate overshoot, and allows a more 
aggressive integral setting.  Larger values cause a more aggressive response.  D‐Part is not 
needed on many steam boilers.  If needed, small values of less than 20 typically work well.  
A setting of 0 deactivates the feature.  Large values will typically cause hunting. 
 
3. Check the load limit parameters (UserMaxLoad, MinLoad, MaxLoad) to verify that they are 
not limiting modulation. 
 
4. Check  the  load  mask  parameters  under  each  fuel  and  verify  that  they  are  not  preventing 
modulation.  These can be checked using the following menu path: 
 
 
Params & Display > RatioControl > Gas/Oil Settings > LoadLimits   
 
 
 
Default values are: LoadMaskLowLimit = 0%, LoadMaskHighLimit = 0%. 
 
5. If the LMV5 goes to high fire in phase 52, check parameter StartPointOp under each fuel. 
This should typically be set to 1 (low fire). 
 
 
Note:    If  PID  values  are  set  properly,  the  load  should  change  no  more  than  once  every  8 
seconds  on  most  installations.    If  PID  values  are  set  improperly,  the  duty  cycle  of  the  SQM... 
actuator can be exceeded. 
 
 
Section 7 
 
LMV5 Will Not Modulate Properly 
Page 12 
HOME
LMV Series 
SCC Inc. 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents