DeaO2/Stp36  –  Energizing  input  X5‐03.2  disables  O
Energizing input X5‐03.3 allows the LMV5 to progress past phase 36.  If X5‐03.3 is de‐energized, the LMV5 will remain 
in phase 36 indefinitely. 
CoolFctStby – This setting has no effect (LMV50 only). 
AutoDeactO2  –  Energizing  input  X5‐03.3  will  deactivate  O2  trim  by  setting  O2  trim  OptgMode  to  auto  deact.    O2  trim 
OptgMode must be set to ConAutoDeac for this function to work.  De‐energizing X5‐03.3 sets the O2 trim OptgMode 
back to ConAutoDeac.  Terminal X5‐03.2 has no function with this setting. 
 
 
SCC Inc. 
 
 
  trim,  while  de‐energizing  X5‐03.2  enables  O
2
Page 50 
HOME
Technical Instructions 
LV5‐1000 
  trim  (LMV52  only).  