Ignitionpos - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
PrepurgePosAir (S)
Params & Display>
PrepurgePosAux1 (S)
RatioControl>
Gas/Oil Settings>
PrepurgePosAux2 (S)
SpecialPositions>
PrepurgePosAux3 (S)
PrepurgePos
PrepurgePosVSD (S)
IgnitionPosGas or
IgnitionPosOil (S)**
IgnitionPosAir (S)**
Params & Display>
RatioControl>
IgnitionPosAux1 (S)
Gas/Oil Settings>
SpecialPositions>

IgnitionPos

IgnitionPosAux2 (S)
IgnitionPosAux3 (S)
IgnitionPosVSD (S)
PostpurgePosGas or
PostpurgePosOil (S)
PostpurgePosAir (S)
Params & Display>
RatioControl>
PostpurgePosAux1 (S)
Gas/Oil Settings>
SpecialPositions>
PostpurgePosAux2 (S)
PostpurgePos
PostpurgePosAux3 (S)
PostpurgePosVSD (S)
SCC Inc.
Default
Range
90 deg
0-90 deg
Sets the prepurge position of the air actuator. Be aware of mechancial stops.
90 deg
0-90 deg
Sets the prepurge position of the aux1 actuator. Be aware of mechancial stops.
90 deg
0-90 deg
Sets the prepurge position of the aux2 actuator. Be aware of mechancial stops.
90 deg
0-90 deg
Sets the prepurge position of the aux3 actuator. Be aware of mechancial stops.
100%
0-100%
Sets the prepurge speed of the VSD.
Sets ignition position of the fuel actuator(s). If one fuel actuator is connected to both the gas
Not Set
0-90 deg
and oil valve, it can still have independent ignition positions for gas and oil. Setting is
independent of low fire. Be aware of mechancial stops.
Sets ignition position of the air actuator. Setting is independent of the low fire position. Be
Not Set
0-90 deg
aware of mechancial stops.
Sets ignition position of the aux1 actuator. Setting is independent of the low fire position. Be
Not Set
0-90 deg
aware of mechancial stops.
Sets ignition position of the aux2 actuator. Setting is independent of the low fire position. Be
Not Set
0-90 deg
aware of mechancial stops.
Sets ignition position of the aux3 actuator. Setting is independent of the low fire position. Be
Not Set
0-90 deg
aware of mechancial stops.
Not Set
0-100%
Sets ignition speed of the VSD. Setting is independent of the low fire position.
15 deg
0-90 deg
Sets the postpurge position of the fuel actuator(s). Be aware of mechancial stops.
15 deg
0-90 deg
Sets the postpurge position of the air actuator. Be aware of mechancial stops.
25 deg
0-90 deg
Sets the postpurge position of the aux1 actuator. Be aware of mechancial stops.
25 deg
0-90 deg
Sets the postpurge position of the aux2 actuator. Be aware of mechancial stops.
25 deg
0-90 deg
Sets the postpurge position of the aux3 actuator. Be aware of mechancial stops.
50%
0-100%
Sets the postpurge speed of the VSD.
Page 18
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x
x
x x
x x
x x x
x x x
x x x
x x
x
x
x
x
x x x
x x
x
x x x
x x
x x
x
x