VSD Module Software Update: Version 0130 to 0140
The following updates were made with LMV52 VSD module software version 0140:
1. Opening of the release contact during shutdown can be set via parameter
ReleaseContctVSD. This enables the VSD module to use a DC break.
2. Quick shutdown of the burner when speed deviation exceeds parameter TolQuickShutdown.
VSD Module Software Update: Version 0140 to 0150
The following updates were made with LMV5 VSD module software version 0150:
1. To avoid error code A9, diagnostic 18 (Page disrupted), statistics data are now only stored in
standby and operation.
2. In some cases, the correction offset for the speed setpoint was not reset after a safety
shutdown. This could lead to error messages. The new version eliminates this effect.
3. Internal system tests have been modified, allowing the VSD test initialized by the LMV5 to be
dropped.
4. Quick shutdown of the VSD is also affected in programming mode.