Additional Tips For Commissioning - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
Additional Tips for Commissioning  
 
If  an  LMV52  is  being  commissioned,  activate  the  O
sensor  is  heated,  this  will  show  a  fast  responding  O
Control Curve commissioning.  This sensor reads %O
than an external flue gas analyzer. 
 
Using a fuel flow meter (temporary or permanent) for commissioning is always a good idea even 
for LMV51's without O
the  PID  loop  in  any  load  control  will  work  much  better.    A  temporary,  insertion  type  of  flow 
meter is available from SCC Inc. for this purpose. 
 
If burner head pressure must be used as a last resort to estimate firing rate, bear in mind that 
head  pressure  does  not  increase  with  gas  flow  in  a  linear  manner.    There  is  a  square  root 
relationship  between  the  differential  pressure  across  the  burner  head  and  the  gas  flow.    This 
relationship is very similar to how the pressure varies across a fixed orifice with an increase or 
decrease in flow.  Also, furnace pressure must be accounted for by hooking up both sides of the 
manometer, one side to the burner head pressure and one side to the furnace pressure. 
 
Carbon Monoxide (CO) is produced when combustion is incomplete, typically due to the flame 
being  too  rich  or  too  lean.    CO  is  potentially  explosive  when  mixed  with  air  in  the  right 
proportions.    For  CO  to  be  explosive  in  air,  it  must  reach  a  concentration  of  at  least  12.5% 
(125,000 ppm) with an ignition source present. 
 
If a burner is commissioned properly, actuator curves should increase smoothly with increasing 
load  (firing  rate).    One  exception  to  this  would  be  the  FGR  actuator  (Aux1  or  Aux3)  which 
commonly decreases (closes) as firing rate increases.  Curves should always be smooth, with no 
sharp corners. 
 
The  best  and  fastest  method  to  commission  a  burner  with  an  LMV5  is  to  set  up  a  small  table 
where the technician can have his laptop, AZL, fuel flow meter and external flue gas analyzer all 
within  arm's  reach.    This  allows  the  curve  points  to  be  input  rapidly  and  accurately.    If  the 
information  is  entered  in  the  laptop  point  by  point,  a  very  nice  start‐up  report  will  also  be 
generated. 
 
The ACS450 software is not as fast as using the AZL to commission the LMV5.  Since this is the 
case, the ACS450 is typically not used to commission the LMV5.  However, the ACS450 is very 
valuable when used to download an .mdb file (all parameter settings, fault and lockout history, 
in English) and also when used to download .par files (the machine‐language parameter set from 
the  LMV5).    It  is  recommended  to  download  both  of  these  files  after  commissioning,  so  that 
there is a backup record of all parameter and curve settings. 
 
To go back out of the menu and check burner operation, press the < and > buttons at the same 
time.    This  will  take  the  cursor  to  Normal  Operation,  so  the  normal  operation  screen  can  be 
viewed by pressing Enter.  This can be done anywhere in the menu as long as a single parameter 
is not currently displayed.  Pressing Esc will take the cursor back in to where it was in the menu.  
 
Section 4 
 
 trim.  If the fuel input (heat output) increases linearly with firing rate, 
2
Page 28 
HOME
  sensor  as  soon  as  possible.    Once  the  O
2
  value  on  the  AZL  screen  during  Ratio 
2
 wet so the value will be somewhat lower 
2
LMV Series 
 
2
SCC Inc. 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents