Gasfiring - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
GasFiring (U)
OilStage1/Mod (U)
Operation>
OilStage2 (U)
HoursRun
OilStage3 (U)
TotalHoursReset (U)
TotalHours (U)
SystemOnPower (U)
GasStartCount (U)
Operation>
OilStartCount (U)
StartCounter
TotalStartCountR (U)
TotalStartCount (U)
Curr Flow Rate (U)
Volume Gas (U)
Volume Oil (U)
Operation>
Fuel Meter
Volume Gas R (U)
Volume Oil R (U)
Reset Date Gas (U)
Reset Date Oil (U)
LockoutCounter (U)
Operation
Current O2 Value (U)
O2 Setpoint (U)
Operation>
SupplyAirTemp (U)
O2 Module
FlueGasTemp (U)
CombEfficiency (U)
Operation
BurnerID (U)
InterfacePC (U)
GatewayBASon (U)
Operation>
GatewayBASoff (U)
OptgModeSelect
Gateway status (U)
Type of Gateway (U)
SCC Inc.
Default
Range
Hours run firing gas. Reset / adjust: Params & Display > HoursRun
Hours run on modulating or stage 1 oil. Reset / adjust: Params & Display > HoursRun
Hours run on stage 2 oil. Reset / adjust at: Params & Display > HoursRun
Read Only
Hours run on stage 3 oil. Reset / adjust at: Params & Display > HoursRun
Hours run on all fuels. Reset / adjust: Params & Display > HoursRun
Displays the number of hours run on all fuels. Not resettable.
Hours the system has been powered. Not resettable.
Number of startups on gas. Reset at: Params & Display > StartCounter
Number of startups on oil. Reset at: Params & Display > StartCounter
Read Only
Number of startups on all fuels. Reset at: Params & Display > StartCounter
Displays the number of startups on all fuels. Not resettable.
Displays the current flow rate of fuel, gas or oil.
Read Only
Totalized volume of gas since the last reset.
Totalized volume of oil since the last reset.
Resets the totalized volume of gas.
Reset Only
Resets the totalized volume of oil.
Displays the date when the volume of gas was last reset. Cannot be changed.
Read Only
Displays the date when the volume of oil was last reset. Cannot be changed.
Read Only
Displays the total number of lockouts that have occurred.
Current O2 sensor reading. Wet basis - will be lower than dry O2 reading.
O2 target value for the current load can be viewed here.
Current combustion air temperature if equipped with ambient temp sensor.
Read Only
Current flue gas temperature if equipped with flue gas temp sensor.
The calculated value of the combustion efficiency based on the wet O2 value, combustion air
temperature, and flue gas temperature.
Read Only
Burner identification. Adjust at: Updating > BurnerID (requires OEM password)
press Enter to activate,
This activates COM 1, the DB9 connector on the front of the AZL to use with ACS450.
press Esc to deactivate
press Enter to activate
This activates or deactivates COM 2, the RJ45 jack on the bottom of the AZL, for Modbus or
eBUS communication. This port uses RS-232 communications.
press Enter to deactivate
Read Only
Displays if the gateway is activated or deactivated.
Modbus
This parameter configures the protocol of Com 2. Select the proper communication protocol
Modbus
eBus
(Modbus, eBUS) or select 'Data output' for use with trending software.
Data output
Page 6
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x
x x x
x x
x x x
x x x
Section 3