Figure 6‐7:  Example of Typical Lambda Factor for O
 
The Lambda Factor curves serve as a tool to evaluate how accurate and repeatable the fundamental 
mechanical systems of the burner are and how well all the curves were commissioned.  In general, the 
Lambda Factor curve should be as constant or "flat" as possible.  The actual numerical value is not 
important, but the consistency between points is.   An approximate guide for evaluation of the Lambda 
Factor: 
 
Difference in Lambda Factor between adjacent points ‐> lower numbers are better.  Max = 0.45 
(Higher numbers may lead to O
Standard Deviation of all points on the curve ‐> lower numbers are better.  Max = 0.40 (Higher 
numbers may lead to O
 
SCC Inc. 
 
 
 
 trim deactivations on some burners during modulation). 