Introduction; O 2 Trim (O 2 Control) Fundamentals - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
Introduction  
 
The LMV52.240 and the LMV52.440 both have O
"monitor") capability.  In addition, the LMV52.440 offers advanced features such as temperature 
compensated light‐off and more dynamic O
recommended for more difficult applications such as low and ultra‐low NOx burners where the burner 
stability band is much smaller than a traditional nozzle mixing burner.  Some features in the LMV52.440 
were specifically designed for ultra‐low NOx mesh burners. 
 
The O
 trim functions by using an in‐situ O
2
actuators and / or VSD to maintain a % O
adjusted, thus the O
 trim does not adjust the firing rate (fuel‐related load).  Only the air rate (air‐related 
2
load) is adjusted. 
 
Each Ratio Control Curve Point that is entered (see Section 4) will have a corresponding O
rich limit (O
 alarm) and lean limit (O
2
performed on Point 1.  If 10 points are entered on the Ratio Control Curve, there will be 9 trim points 
and 10 rich limit (O
 alarm) points.  Having 10 points on the Ratio Control Curve is recommended. 
2
 
As is the case with advanced systems such as O
advanced system must be in place and working correctly to enable the advanced system to work 
correctly.  For example, if the gas pressure supply is not repeatable upstream of the firing rate control 
valve (fundamental system), then the O
fundamental systems on the burner / boiler that must be working correctly are outlined in detail in the 
Pre‐Requisites listed in Section 4.  The Pre‐Requisites for LMV52 systems with O
before O
 trim commissioning is attempted. 
2
 
If the Pre‐Requisites are satisfied, then reliable operation of the O
settings for the application and correct commissioning of the O
behind how the O
 trim system operates, and will outline the typical commissioning procedure for a 
2
traditional nozzle mixing burner (standard emissions) and a pre‐mix mesh burner (low or ultra‐low NOx). 
Nozzle mixing burners that use a high percentage of FGR to achieve low NOx typically behave in a way 
that is similar to a pre‐mix mesh burner, so the commissioning procedure for these types of burners is 
similar to a pre‐mix mesh burner. 
 
O
 Trim (O
 Control) Fundamentals 
2
2
 
By definition, an O
 trim (O
2
and adjusts the fuel or air flow to maintain an O
the %O
 (wet basis) with an in‐situ O
2
actuators.  If the burner is equipped with a VSD (variable speed drive) for the blower, the O
also adjust the blower speed to influence the burner airflow. 
 
 
 
 
Section 6 
                                                          Page 2                                                                         SCC Inc. 
 
 (oxygen) trim and O
2
 trim capabilities.  In general, the LMV52.440 is 
2
 sensor installed in the boiler stack, and then adjusting 
2
 setpoint.  Only air‐related (air influenced) actuators are 
2
 max value).  The exception to this rule is that O
2
 trim, the fundamental systems that lie underneath the 
2
 trim (advanced system) is likely to deactivate.  The 
2
 control) system monitors the level of O
2
 setpoint.  The LMV52 accomplishes this task by reading 
2
 sensor and by adjusting the angular position of air flow influencing 
2
HOME
 alarm (previously called 
2
 trim cannot be 
2
 trim must be met 
2
 trim depends on correct parameter 
2
 trim.  This section will outline the basics 
2
 in the exhaust gases of the boiler 
2
LMV Series 
 trim setpoint, 
2
 trim can 
2
 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents