CANbus Faults Including "AZL not on Bus" and "System Test" (continued) 
 
3. Check the LMV5 fault history.  If the faults always occur in phase 38, the CANbus errors are 
being caused by noise from the ignition transformer.  Make sure the ignition transformer is 
grounded properly and has a good neutral.  Also, make sure any CANbus wires that run 
close to the ignition transformer are in proper conduit.  It may be necessary to either 
relocate the ignition transformer or add a shield between the ignition transformer and any 
nearby CANbus wires. 
 
4. Unplug the 6‐pin green connector plugged into terminal X51 on the top of the LMV5.  This 
leaves the AZL, the LMV5, and the cable between them as the only CANbus components still 
plugged in.  Reset the fault on the LMV5.  At this point, two things can happen: 
 
 If the AZL faults with "Fault Feedback Air Actuator", then the AZL, the LMV5, and the 
cable between them are all working properly.  This means that there is likely an issue 
with the wiring of the actuators or O
 
 If the same CANbus fault recurs, then there is a problem with the AZL, the LMV5, or 
the cable between them.  Check the wiring and terminations on the cable.  Though 
unlikely, the AZL or the LMV5 might be damaged and need to be replaced.  If a spare 
AZL is available, try it.  If no spare AZL is present, check for any noticeable damage to 
either the AZL or the LMV5 to determine which component to replace. 
 
5. To find the wiring issue with the actuators or O
time to terminal X51 on the LMV5 to determine which component is causing the CANbus 
errors.  First, plug in just the cable (unplugged from the actuator) that connects the first 
actuator to terminal X51 on the LMV5.  Reset the fault on the LMV5.  If "Fault Feedback Air 
Actuator" shows up again, the cable itself is okay.  Next, plug in just the first actuator 
(unplugged from the cable running to the second actuator).  Reset the fault on the LMV5.  
As long as actuator feedback faults continue to show up after each component is plugged in 
and the LMV5 is reset, continue to plug in another component.  At some point, plugging in a 
component should cause the CANbus fault to recur. 
 
6. Once the component causing the CANbus errors has been found, check the following to 
correct the problem: 
 
 Make sure all terminations to the actuator are done properly and no wire strands 
from adjacent pins are touching one another and causing a short. 
 
 
 
 
Section 7 
 
 module.  Go to step 5. 
2
 module, plug components back in one at a 
2