LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
Params & Display>
Autom/Manual/Off (U)
RatioControl
OperatRampMod (S)
Params & Display>
RatioControl>
OperatRampStage (S)
Times
TimeNoFlame (S)
NumFuelActuators (O)
ShutdownBehav (S)
Params & Display>
RatioControl
ProgramStop (S)
Pos. Tolerance (O)
SCC Inc.
Default
Range
Three options exist:
1) Automatic - Enables the burner allowing it to respond to setpoints and switch on / switch
Automatic
off points.
Automatic
Burner off
2) Burner off - Manually turn the burner off.
3) Manual - Enables the load of the burner to be set with SetLoad . When in manual,
Manual
setpoints and switching points are ignored. If terminal X5-03.1 (burner switch) is enabled, it
must be energized for the LMV5 to start regardless of parameter setting.
Controls the speed at which the actuators / VSD will ramp during phase 60-62 (fuel valves
30s
30-120s
open). Higher numbers are slower ramps. Set for slowest actuator.
(SQM45 - 10s, SQM48.4 - 30s, SQM9 - 30s, SQM48.6 - 60s)
10s
10-60s
Controls the speed at which the LMV5 will ramp in multistage operation.
Controls the speed at which the actuators / VSD will ramp when the fuel valves are closed.
10s
10-120s
Higher numbers are slower ramps. Set for slowest actuator.
(SQM45 - 10s, SQM48.4 - 30s, SQM9 - 30s, SQM48.6 - 60s)
Setting is avalable so that a single fuel actuator could be used for a gas and oil valve on a
2
1-2
common shaft. Also useful if firing 2 gaseous fuels with the same firing rate control valve.
HomePos
Controls the position of the actuators / VSD when a lockout occurs. Set to the safest option
HomePos
PostpurgeP
for the burner.
Unchanged
For gas or oil firing, this parameter will stop the sequence in the selected phase. Useful for
commissioning and service work.
See
deact
The LMV5 can be held in the following phases: 24 Prepurge, 32 Prepurge FGR, 36 Ignition
Description
Position, 44 Interval 1 (pilot stabilize), 52 Interval 2 (main flame stabilize), 72 Postpurge
Position, 76 Postpurge FGR. Stop can also be deactivated.
Sets the allowable tolerance on actuator positions and VSD speed. A setting of 0.3°/0.5%
0.3-1.2°/
means that all actuators must be within +/-0.3° of their required positions, and the VSD must
0.3°/0.5%
0.5-1.2%
be within +/-0.5% of its required speed. Can be increased from the default values to
eliminate nuisance lockouts from a fluttering damper.
Page 21
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
Section 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents