LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
Max Stat Dev (U)
Max Dyn Dev (U)
Params & Display>
VSD Module>
Num Dev >0.3% (U)
Process Data
Num Dev >0.5% (U)
Absolute Speed (U)
ProductionDate (U)
Params & Display>
VSD Module>
SerialNumber (U)
ProductID
ParamSet Code (U)
ParamSet Vers (U)
Params & Display>
SW Version (U)
VSD Module
O2 Sensor (S)
Params & Display>
O2SensServTim (S)
O2 Module>
Configuration
O2SensServTimRes (S)
SupAirTempSens (S)
SCC Inc.
Default
Range
Read Only
Read Only
Read Only
Read Only
Read Only
ASN (U)
Read Only
Read Only
no sensor
no sensor
QGO20
QGO21
0 days
0-65535 days
activated
deact
deactivated
no sensor
no sensor
Ni1000
Pt1000
Records the maximum VSD speed deviation from setpoint during steady state operation
(steady load) during a run period. 0 to 100% of standarized speed.
Maximum motor speed deviation from setpoint during an acceleration or deceleration of the
motor (changing load) during a run period. Range = 0 to 100%
The number of speed deviations exceeding 0.3% of the standardized speed at the end of a
modulation event. Max = 255 deviations.
The number of speed deviations exceeding 0.5% of the standardized speed at the end of a
modulation event. Max = 255 deviations.
This displays the real time speed of the blower motor in RPM. Max is 6553 RPM.
Information concerning the VSD board (pieces internal to the LMV5).
Software version of the VSD control.
Configures the PLL module for the connected O2 sensor.
Sets the service interval for the O2 sensor. The time set here is compared against the total
hours run counter. See Operation > HoursRun . Upon expiration of service interval, different
actions will be taken based on O2 trim operating mode. If in 'conAutoDeac', then O2 trim
will auto deactivate. If operating mode is set to 'O2 Control' or 'O2 Alarm', a lockout will
occur. If set to 0, feature is deactivated.
Resets the service interval for the O2 sensor. Reset once service work has been completed.
Configures the PLL module for the appropriate ambient air temperature sensor. Sensor is
not required for O2 trim, but is required for the efficiency calculation.
Page 40
HOME
P - LIST
Description
Technical Instructions
LV5-1000
LMV
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
Section 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents