Siemens LMV5 Series Technical Instructions page 180

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
NOTE:  Both sensors are required to do a boiler efficiency calculation.  The boiler efficiency 
calculation is not required for O
or not wired correctly, the O
perform a temperature‐compensated startup on the LMV52.440. 
 
4. Set the appropriate actuators to "air influen" (air influenced).  These are typically only the actuators 
/ VSD that will directly influence the burner air rate.  The menu path for these parameters is: 
 
 
Params & Display > RatioControl > Gas Settings 
 
Typically, only the air actuator and the VSD (if used) are set to air influenced.  If used, the FGR 
actuator is usually not set to air influenced. 
 
5. Set the operating mode of the O
for the O
 system curves to be commissioned.  The menu path for this parameter is: 
2
 
Params & Display > O2Contr/Alarm > Gas Settings > OptgMode = man deact 
 
6. Set the curve point at which the low fire delay time will be measured. This is typically set to Point 2, 
unless oversized exhaust stacks with high turndown burners are encountered, which may make gas 
velocity in the stack too low at low fire.  For these applications, setting this parameter to a higher 
point than Point 2 will increase the gas velocity past the O
reading.   This can be set through the following menu path: 
 
Params & Display > O2Contr/Alarm> Gas Settings > Control Param > LowfireAdaptPtNo 
 
7. Set the load value at which the O
Point 2 on the Fuel‐Air Ratio Control Curve.  The exception to this is if parameter LowfireAdaptPtNo 
is set to a point other than Point 2.  If this is the case, set this for the load value that corresponds to 
the point set by LowfireAdaptPtNo.  This can be set through the following menu path: 
 
Params & Display > O2Contr/Alarm > Gas Settings > Control Param > O2 CtrlThreshold 
 
8. Set the desired type of pre‐control.  For most natural gas burners where the gap between O
is large enough that the Lambda Factor can be learned (see O
6‐2), this should be set to "like P air". The "like theory" setting is typically used for oil burners, and 
"LambdaFact1" should only be used as a last resort.  The menu path for setting the type of pre‐
control is: 
 
Params & Display > O2Contr/Alarm > Gas Settings > Control Param > Type Air Change 
 
 
 
 
 
 
 
Section 6 
                                                          Page 8                                                                         SCC Inc. 
 
 trim operation.  If sensors are activated but not reading correctly 
2
 trim will not activate.  Burner inlet temperature must be read to 
2
 system to "man deact" (manually deactivated).  This is necessary 
2
 trim will disengage.  Typically, this is set to the load value for 
2
HOME
 sensor and yield a more responsive O
2
 Control and O
 Alarm Curves in Figure 
2
2
LMV Series 
 
2
 curves 
2
 