LMV Series 
 
 
4. InitContr – O
 control is preparing to engage but is still locked 
2
5. LockTLoad – O
 control is engaged but locked (in pre‐control) due to a load change 
2
6. Active – O
 control is actively trimming based on setpoint and measured O
2
7. LockTCAct ‐ O
 control is engaged but locked due to an excursion from setpoint 
2
 
If the state of the O
 control is shown as "locked", parameter Diag Reg State will show the reason why. 
2
 
Diag Reg State 
Menu path:  Params & Display > O2 Contr/Alarm > Process Data 
 
This parameter shows the reason that the O
0 – The load is below the load limit set by parameter O2 CtrlThreshold 
1 – The load controller is in auto tune 
2 – The O
 sensor is being tested for response (self‐check of O
2
3 – The fuel‐air ratio or O
2
4 – The measured % O
 is above the lean limit or below the rich limit 
2
5 – There is an error in the PLL52 module 
6 – There is an error in the pre‐control 
 
Using the O
 Alarm Functionality without O
2
 
As was previously mentioned, the O
parameter OptgMode, which can be found using the following menu path: 
 
Menu path:  Params & Display > O2 Contr/Alarm > Gas/Oil Settings 
 
The available operating modes are: 
1. Man deact ‐ deactivates all O
2. O2 Limiter ‐ Only the O
MaxValue) is exceeded for a time longer than what is set for parameter Time O2 Alarm.  Likewise, a 
lockout will occur if the rich limit (O
parameter Time O2 Alarm.  No trim functionality is active. 
3. O2 Control ‐ The same as O2 Limiter, except O
will cause a lockout in the same way as the O2 Limiter mode. 
4. ConAutoDeac – In this mode, exceeding the rich or lean limits will not cause an immediate lockout. 
Exceeding the rich or lean limits will cause the O
time of 3 times Tau, the measured %O
the O
 trim will be deactivated.  If the %O
2
trim can be automatically deactivated and reactivated the number of times allowed by parameter 
NumMinUntilDeact.  The maximum setting is 5.  If more than 5 deactivations and reactivations 
occur, then the O
 trim mode will be changed to "auto deact" until the O
2
re‐activated.  
5. Auto deact ‐ indicates that the O
error codes in Section 7.  Do not select this mode. 
 
 
 
SCC Inc. 
 control is locked.  Possible values are: 
2
 trim curves are being programmed 
 Trim 
2
 system can be run in different modes.  The modes are set using 
2
 trim and O
 alarm functionality.  %O
2
2
 alarm is active.  This means that a lockout will occur if the lean limit (O2 
2
 alarm curve) is exceeded for a time longer than what is set for 
2
 trim is now enabled.  Exceeding rich or lean limits 
2
 will be re‐evaluated.  If the %O
2
 is lower than the rich alarm, a lockout will occur. The O
2
 trim has been automatically deactivated for some reason.  See 
2
Page 25 
HOME
 
 
 sensor) 
2
 value can still be viewed. 
2
 trim to be temporarily deactivated.  After a waiting 
2
 is higher than the rich alarm, 
2
 trim control is manually 
2
Technical Instructions 
Document No. LV5‐1000 
 value 
2
 
2
Section 6 
 