Gaspressuremax - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
RotSpeed PS on (S)
RotSpeed PS off (S)
InputController (O)
Params & Display>
Config X5-03 (S)
BurnerControl>
Configuration>
ConfigIn/Output
GasPressureMin (O)
GasPressureMax (O)
OilPressureMin (O)
OilPressureMax (O)
SCC Inc.
Default
Range
If FGR-PS/FCC is set to PS VSD, then INPUT X4-01.3 must be energized from this % VSD and
80%
0-100%
higher. Must be set higher than RotSpeed PS off .
If FGR-PS/FCC is set to PS VSD, then INPUT X4-01.3 must be de-energized from this % VSD
50%
0-100%
and lower. Must be set lower than RotSpeed PS on .
Sets the function of INPUT X5-03.1. If activated, X5-03.1 must be energized to permit the
LMV5 to fire. This setting is typically used with a hardwired burner on-off switch. On an
activated
LMV5 equipped with an internal load controller (LMV51.1 and higher), the internal load
activated
deactivated
controller may remove the call for heat and shut down the burner even if X5-03.1 is
energized. If deactivated, X5-03.1 has no function when in any internal load control mode.
The LMV5 can also be given permission to fire via Modbus if X5-03.1 is deactivated.
Sets the function of INPUTS X5-03.2 and X5-03.3.
1) LMV5x std - floating bumping load control is retained.
LMV5x std
2) LMV2/3 std or LMV2/3 inv - normal or inverted LMV5 2/3 staged oil functionality.
LMV2/3 std
3) DeaO2/Stp36 - energizing terminal X5-03.2 disables O2 trim and de-energizing enables O2
LMV2/3 inv
trim (LMV52 only). Also, energizing terminal X5-03.3 allows the LMV5 to progress past phase
LMV5x std
DeaO2/Stp36
36 (de-energizing stops the LMV5 in phase 36 indefinitely).
CoolFctStby
4) CoolFctStby - only used on an LMV50.
AutoDeactO2
5) AutoDeactO2 - energizing X5-03.2 will deactivate the O2 trim by setting the O2 trim mode
to "auto deact". O2 trim mode must be set to "ConAutoDeac" for the AutoDeactO2 to
function. De-energizing sets trim mode back to "ConAutoDeac".
Sets the function of INPUT X9-03.4 for the low gas pressure switch.
activated
1) activated - input is expected to be energized when firing gas, or when using any oil train
activated
deactivated
that requires a gas pilot.
deact xOGP
2) deactivated - terminal has no function.
3) deact xOGP - input is expected to be energized only when firing gas.
activated
Sets the function of INPUT X9-03.3 for a high gas pressure switch. Activate for gas fired
activated
deactivated
installations that use a high gas pressure switch.
Sets the function of INPUT X5-01.2 for a low oil pressure switch.
activated
1) activated - input is expected to be energized by phase 38.
activated
deactivated
2) deactivated - terminal has no function.
act from ts
3) act from ts - input is expected to be energized by phase 40.
activated
activated
Sets the function of INPUT X5-02.2 for the high oil pressure switch.
deactivated
Page 13
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x
x x
x x x
/ / /
x x
x
Section 3