Example: Temperature Sensor Wired To Terminal X60 - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
Remote Setpoint (continued)

Example: Temperature Sensor Wired to Terminal X60

LC_OptgMode = IntLC X62
Ext Inp X62 U/I = 4..20 mA
MeasureRangePtNi = 302 °F
Desired remote setpoint range = 180-270 °F
A 4-20 mA signal on terminal X62 scales the setpoint from 32-302 °F. Parameters "Ext
MinSetpoint" and "Ext MaxSetpoint" need to be utilized to get the appropriate setpoint range.
With these parameters set, the following input signals will scale the setpoint accordingly:
4 – 12.8 mA = 180 °F (limited by "Ext MinSetpoint")
12.8 – 18.1 mA = 180 - 270 °F
18.1 - 20 mA = 270 °F (limited by "Ext MaxSetpoint")
SCC Inc.
180℉ − 32℉
=
302℉ − 32℉
270℉ − 32℉
=
302℉ − 32℉
Page 33
HOME
Technical Instructions
Document No. LV5-8000
148
=
= 55%
270
238
=
= 88%
270
Appendix A