Siemens LMV5 Series Technical Instructions page 195

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
NumberTauSuspend ‐ The length of time after main flame light‐off that is required until an accurate, 
representative O
 value is read by the O
2
the boiler with products of combustion.  This parameter is a multiplier that is taken times the delay time 
at low fire (Tau Low‐Fire) to determine the length of waiting time before a representative O
measured and the O
 trim can engage. 
2
 
If Tau Low‐Fire was read to be 5 seconds during O
NumberTauSuspend is set to 10, then the O
 
A setting of 10 will work for almost all applications, and will be conservative for most.  Higher numbers 
(more waiting time) are more conservative and lower numbers are less conservative. 
Menu path:  Params & Display > O2Contr/Alarm > Gas Settings > Startmode 
 
Startmode ‐ This determines how the burner transitions from light‐off to engaging the O
the modes, "Ign Load TC" and "IgnPtWithTC", require a combustion air temperature sensor. 
 
Immediately after main flame light‐off, the O
the boiler is full of air.  Some burner designs, most notably ultra‐low NOx mesh burners, require some 
type of compensation at light‐off to ensure flame stability before the O
options are available: 
 
1. Standard ‐ Burner will modulate right after light‐off, not waiting for the O
will engage after the time defined by NumberTauSuspend expires at the burner's current load. 
2. Ign Load TC ‐ This will vary the ignition positions (special positions) of the actuators based on the 
combustion air temperature and also based on a defined load number (parameter Load of Ignition). 
This also will drive the "temperature compensated" actuators to Point 2 (or whichever point is 
defined by parameter StartPointOp).  The burner will be held in Phase 60 at Point 2 (or whichever 
point is defined by parameter StartPointOp) until the time defined by NumberTauSuspend expires.  
The burner will then be released to modulate with the O
3. IgnPtWithTC ‐ This will not vary the ignition positions (special positions) of the actuators based on 
the combustion air temperature.  It will drive the actuators from the temperature‐compensated set 
ignition positions to Point 2 (or whichever point is defined by parameter StartPointOp).  The burner 
will be held in Phase 60 at Point 2 (or whichever point is defined by parameter StartPointOp) until 
the time defined by NumberTauSuspend expires.  The burner will then be released to modulate with 
the O
 trim active.  
2
4. IgnPtWoutTC ‐ Similar to "IgnPtWithTC", but less accuracy due to the lack of a combustion air 
sensor.   
 
On burners with a wide flame stability band, such as traditional nozzle mixing burners with little or no 
FGR, a StartMode setting of "standard" typically works well.  On burners with a more narrow flame 
stability band (low and ultra‐low NOx mesh burners), "IgnPtWithTC" typically works well. 
Menu path:  Params & Display > O2Contr/Alarm > Gas Settings > Startmode 
 
 
 
 
 
SCC Inc. 
 
 
 sensor.  Basically, the time it takes to replace all of the air in 
2
 Control Curve commissioning, and 
2
 trim would engage 50 seconds after main flame light‐off.  
2
 sensor does not have a valid reading since the gas path of 
2
 trim active. 
2
Page 23 
HOME
Technical Instructions 
Document No. LV5‐1000 
 value is 
2
 trim. Two of 
2
 sensor has a valid reading.  Four 
2
 trim to engage.  O
2
Section 6 
 trim 
2
 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents