LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
PostpurgeLockout (S)
Params & Display>
BurnerControl>
Times>
TimesGeneral
MaxTmeStartRel (S)
AlarmStartPrev (S)
Standby Error (S)
NormDirectStart (S)
Params & Display>
BurnerControl>
OilPumpCoupling (S)
Configuration>
ConfigGeneral
IgnOilPumpStart (S)
ForcedIntermit (S)
Skip PrepurgeGas (S)
Skip PrepurgeOil (O)
SCC Inc.
Default
Range
If a lockout condition occurs, and the combustion air fan was running, it will continue
running in the lockout phase (phase 00) for this period of time. This time replaces the
120s
0.2s-63min
postpurge time in the event of a lockout. If the combustion air fan was not running, the fan
will remain off for the rest of the lockout phase.
When the LMV5 gets a call for heat, this is the maximum time the LMV5 will hold in phase 21
waiting for a start release. If this time expires and the start release is not made, the LMV5
120s
0.2s-63min
will go into alarm.
See: Params & Display > BurnerControl > Times >TimesStartup1 > MinTmeStartRel
Determines if the alarm OUTPUT X3-01.2 will be energized in the event of a start prevention
activated
deact
(an alarm in standby - Phase 12). AlarmDelay sets how long the LMV5 will wait before going
deactivated
into alarm.
activated
If this is set to activated, an alarm will occur if the safety loop is opened in phase 12
deact
deactivated
(standby). If deactivated, the safety loop can be open when in phase 12 without alarm.
Enables the LMV5 to skip postpurge (T3) time, and go directly into prepurge if there is a call
Normal
NormalStart
for heat during postpurge T1. If set to DirectStart, a 3-way valve on OUTPUT X4-03.3 must be
Start
DirectStart
used to check the air pressure switch.
Combined with IgnOilPumpStart determines the behavior of OUTPUT X6-02.3:
1) Magnetcoupl - the output will energize, in either phase 22 or 38, depending on the setting
Magnet-
Magnetcoupl
of IgnOilPumpStart . Output will de-energize as soon as main oil valves close.
coupl
Directcoupl
2) Directcoupl - the output will energize at the same time as the blower, and de-energizes 15
seconds after the blower.
on in Ph22
If Magnetcoupl is selected above, this determines when OUTPUT X6-02.3 is energized. If a
on in Ph22
on in Ph38
direct spark oil train is selected, spark will occur during prepurge if set to Ph22.
When activated, this setting forces the LMV5 to shut the burner down, every 23 hours 50
activated
activated
minutes. The burner will automatically restart. The purpose of this is to check and cycle
deactivated
safety devices. If a non-self check flame scanner is used, this must be activated.
deact
If activated, prepurge for gas will be skipped. Not recommended for most burners.
activated
deactivated
deact
If activated, prepurge for oil will be skipped. Not recommended for most burners.