Lockouthistory - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
NormalOperation (U)
Status/Reset (U)
OperationalStat
FaultHistory (U)
LockoutHistory (U)
Alarm act/deact (U)
SetpointW1 (U)
Operation>
BoilerSetpoint
SetpointW2 (U)
Operation>
User MaxLoadMod (U)
User Maxload
User MaxLoadStg (U)
CurrentFuel (U)
Operation>
Fuel
FuelSelect (U)
Operation>
Date/TimeOfDay>
TimeOfDay (U)
DisplayClock
Weekday (U)
Operation>
Date/TimeOfDay>
TimeOfDay (U)
SetClock
Weekday (U)
SCC Inc.
Default
Range
Read Only
Reset
Read Only
Read Only
activated
activated
deactivated
0-3632 F
Not Set
0-1449 PSIG
MinLoadGas -
100%
MaxLoadGas
S3
S1-S3
Gas
Gas
Date (U)
Read Only
Date (U)
Set for local date and time
at factory location in
Europe.
The normal AZL52 screen. In standby: Setpoint, Actual Value, Fuel and status can be
displayed. In run: pertinent information will be displayed. Faults and warnings will always
appear on the AZL52. Pressing Enter button will toggle information.
Shows the current fault if there is one, or displays 'No Fault' if there is not.
If a fault is present, it can be reset by pressing Esc, then Enter.
Shows the last 21 faults. All lockouts are faults, not all faults are lockouts. Format: Class,
Fuel, (fault) Code, Phase, Diag(nostic), Lo(a)d and Start No.
Shows the last 9 lockouts. Format : Date, Time of day, C:(code), D:(diagnostic), P:(phase),
Start No., Load, and Fuel.
Functions as an alarm silence. Deactivates OUTPUT X3-01.2 which is the alarm output in the
event of a lockout. Output will automatically reactivate if another lockout occurs or if system
is reset or restarted.
The LMV5 has 2 internal setpoints. SetpointW1 is the normal internal setpoint. SetpointW2
is an alternate internal setpoint. Changeover via dry contact between OUTPUT X62.1 and
INPUT X62.2 if LC_OptgMode is set to IntLC. Contact open = W1, closed = W2. Max setpoint
limited by sensor range (parameter TL_ThreshOff , MRange PressSens , MRange TempSens ,
or MeasureRangePtNi ).
Used to limit the maximum load (firing rate) without a password. For modulating burners.
May be limited by MinLoadGas and MaxLoadGas .
Used to limit the maximum load (firing rate) without a password. For staged burners.
Gas
Displays the fuel that is currently selected via hardwire, AZL52 or Modbus
Oil
If INPUT X4-01.1 and INPUT X4-01.2 are not energized, fuel selection is 'internal' (soft) and
Gas
can be set here or via Modbus. Energize (hard) X4-01.1 for gas or X4-01.2 for oil. Powering
Oil
both terminals at the same time will cause a lockout.
Displays the current date.
Display the current time.
Displays the day of the week.
Sets the date. Select U.S. or European format at: Params & Display > AZL > DateFormat
Sets the time of day. 24 hour format: HH:MM
Sets the day of the week.
Page 5
HOME
P - LIST
Description
Technical Instructions
LV5-1000
LMV
x
x
x
x x x
x x x
x
x
x
x
x x
x x x
Section 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents