Canbus Faults Including "Azl Not On Bus" And "System Test - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
7‐2:  Common Problems 
 
CANbus Faults Including "AZL not on Bus" and "System Test" 
 
The majority of all LMV5 wiring errors are related to the wiring of the CANbus network.  The 
CANbus network includes the following components: 
 
 LMV5 controller 
 AGG5.210 transformer(s) 
 One main fuse (FU1) and two 12VAC fuses (FU2, FU3) 
 AZL display 
 AGG5.643 special CANbus cable 
 SQM45/48/91 actuators 
 PLL52 O
 module (if equipped) 
2
 
An illustration of the CANbus network with a single transformer is shown below in Figure 7‐2.1. 
 
 
 
Figure 7‐2.1:  Illustration of the LMV5 CANbus Network 
Section 7 
 
 
Page 2 