Additional Tips For Burners With Vfd Control - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
7. If working on an un‐configured LMV52, parameters unrelated to the VFD must be set before the VFD 
can be standardized.  These are thoroughly outlined in Section 4 under "Configuring 
(Parameterization of) an LMV5 with a Default Parameter Set".   To summarize, the following must be 
set:  burner ID, fuel train, actuator addresses, actuator directions of rotation, and actuator special 
positions. 
 
8. The LMV52 safety loop must be closed (high limit, low water, burner flange, etc...) or the 
standardization will not occur even if the LMV52 is not in alarm. 
 
9. The burner switch must be off (LMV52 input X5‐03.1 must be de‐energized). 
 
10. The VFD must be in remote mode so that it will respect the run‐stop contact and the analog signal 
from the LMV52. 
 
11. The LMV52 / VFD / blower are now ready to be standardized.  The standardization process can be 
initiated using the following menu path: 
 
Params & Display > VSD Module > Configuration > Speed > Standardization 
 
Set parameter Standardization to "activated".  The air damper should then drive to the pre‐purge 
position and the VFD / blower should ramp up to approximately 60 Hz (100% VFD).  After a few 
seconds at 60 Hz, the VFD / blower should ramp back down to 0 Hz.  The air damper should also 
drive back to home position.  
 
12. Check the standardized speed, which is the product of the standardization, using the following menu 
path: 
 
Params & Display > VSD Module > Configuration > Speed > StandardizedSp 
 
For 2‐pole blowers, the standardized speed should be 3500 RPM, +/‐ 100 RPM.  If the speed is out of 
this range, the drive was most likely not spanned so that 20mA = 62Hz, or the motor is heavily 
loaded (a lot of slip).  The same logic applies to 4‐pole motors, except the speed should be 1700 +/‐ 
100 RPM. 
 
13. If the LMV52 does not have O
of "air influen" using the following menu path: 
 
Params & Display > RatioControl > Gas/Oil Settings > AirActuator = activated 
 
Additional Tips for Burners with VFD Control 
 
Most of the time, speed faults that are seen on the LMV52 are caused by the VFD not being able to 
decelerate the blower when the blower is being ramped down.  If fast ramp times are not critical for 
the application, ramp times can be increased and this should correct the issue.  If fast ramp times 
are necessary, a braking resistor may also be required to achieve the fast ramp down times. 
 
 
Section 5 
                                                          Page 16                                                                          SCC Inc. 
 
 trim, the air damper actuator can be set back to "activated" instead 
2
HOME
LMV Series 
 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents