6.3
Device replacement without removable medium/programming
device
IO devices having this function can be replaced in a simple manner:
● A removable medium (e.g. SIMATIC Micro Memory Card) with stored device name is not
required.
● The PROFINET IO topology must be configured in HW Config.
● The device name does not have to be assigned with the programming device.
The replacement IO device is now assigned a device name from the IO controller. It is no
longer assigned using a removable medium or programming device. The IO controller
uses the configured topology and the relations determined by the IO devices. The
configured target topology must match the actual topology.
Before reusing IO devices that you already had in operation, reset these to factory settings.
Additional information
For additional information, refer to the STEP 7 Online Help and to the PROFINET System
Description (http://support.automation.siemens.com/WW/view/en/19292127) manual.