Setting Up Passive Cooling - Daikin Altherma 3 GEO Series Installer's Reference Manual

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents

Advertisement

5.8 Setting up passive cooling

EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Setup and configuration: See
4
sensor" 
[
  88] (+ the installation manual of the remote outdoor sensor
(delivered as accessory)).
INFORMATION
Restriction: Passive cooling is only possible for:
Heating only models
Brine temperatures between 0 and 20°C
Passive cooling is cooling without using the compressor. Here the brine circuit
must be branched over the cooling fan coils.
Setup
a
b
b
a Thermostat
b Fan coil units
c External circulation pump
d Non-return valve
e Brine pump
f Plate heat exchanger
g Hydro
h Remote outdoor sensor
A thermostat input contact creates a demand for the brine pump to run. For
more information, see
4
cooling" [
 99].
An external circulation pump is required and needs to be controlled by the
external thermostat.
A non-return valve must prevent backflow to the inlet of the passive cooling loop
and force the brine to go through the borehole.
Configuration
None.
"8.2.2  To connect the remote outdoor
c
d
e
f
g
"8.2.12  To connect the thermostat for passive
5
Application guidelines
|
h
Installer reference guide
51