Energy metering
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
#
[9.9.8]
[5-09]
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
#
[9.9.9]
[5-09]
[9.9.A]
[5-0A]
[9.9.B]
[5-0B]
[9.9.C]
[5-0C]
Power consumption control via current sensors
Limit when [9.9.1]=Current sensor:
#
[9.9.3]
[5-05]
In case the current sensors are calibrated, you can specify an offset for the output
of the current sensors. This value will be added to the current output value of the
current sensor.
#
[9.9.E]
[4-0E]
Priority heater
This setting defines the priority of the electrical heaters depending on applicable
limitation. As no booster heater is present, the backup heater will always be
prioritised.
#
[9.9.D]
[4-01]
Energy metering
If energy metering is performed by the use of external power meters, configure the
settings as described below. Select the pulse frequency output of each power
meter in accordance with the power meter specifications. It is possible to connect
up to 2 power meters with different pulse frequencies. If only 1 or no power meter
is used, select 'None' to indicate the corresponding pulse input is NOT used.
Code
Limit: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Code
Limit 1: 0 kW~20 kW
Limit 2: 0 kW~20 kW
Limit 3: 0 kW~20 kW
Limit 4: 0 kW~20 kW
Code
Limit: 0 A~50 A
Code
Current sensor offset: Offset on the
household current measured by the current
sensors.
–6 A~6 A, step 0.5 A
Code
Priority heater
0 None : The backup heater is prioritised.
1 Booster
setting will be reverted back to 0=None and
the backup heater will be prioritised.
2 Backup
prioritised.
10
Configuration
|
Description
Description
Description
Description
Description
heater: After restart, the
heater: The backup heater is
Installer reference guide
191