Daikin Altherma 3 GEO Series Installer's Reference Manual page 27

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents

Advertisement

Heat pump convectors
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heat pump system.
Comfort. In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
Setup
B
a
A Main leaving water temperature zone
B One single room
a Remote controller of the heat pump convectors
b Remote outdoor sensor
For more information about connecting the electrical wiring to the unit, see
"8.2  Overview
of
4
actuators" [
 80].
The heat pump convectors are directly connected to the indoor unit.
The desired room temperature is set via the remote controller of the heat pump
convectors.
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the heat  pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple heat  pump convectors, make sure each one receives the
infrared signal from the remote controller of the heat pump convectors.
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
A
electrical
connections
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
5
Application guidelines
|
b
for
external
and
Value
Installer reference guide
internal
27