Daikin Altherma 3 GEO Series Installer's Reference Manual page 177

Hide thumbs Also See for Altherma 3 GEO Series:
Table of Contents

Advertisement

EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12
#
Code
[5.C]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
Margin
In domestic hot water operation, the following hysteresis value can be set for the
heat pump operation:
#
Code
[5.D]
[6-01]
Example: setpoint (T
)>maximum heat pump temperature–[6‑01] (T
U
Description
WD curve
Note: There are 2 methods to set the weather
dependent curve. See
"10.4.2 2-points
4
curve" [
 142] and
"10.4.3 Slope-offset
4
curve" [
 143] for more information about the
different curve types. Both curve types require 4
field settings to be configured according to the
figure below.
T
DHW
[0-0C]
[0-0B]
T
a
[0-0E]
[0-0D]
T
: The desired tank temperature.
DHW
T
:
The
(averaged)
a
temperature
[0-0E]: low outdoor ambient temperature: –
40°C~5°C
[0-0D]: high outdoor ambient temperature:
10°C~25°C
[0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature: 45°C~[6‑0E]°C
[0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
Description
The temperature difference determining the heat
pump OFF temperature.
Range: 0°C~10°C
10
Configuration
|
outdoor
ambient
–[6‑01])
HP MAX
Installer reference guide
177