5
|
Application guidelines
5.6.1 Permanent power limitation
Installer reference guide
46
#
1
"5.6.1 Permanent power
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) with one permanent
setting.
▪
Limitation of power in kW or current in A.
2
"5.6.2 Power limitation activated by digital
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) via 4 digital inputs.
▪
Limitation of power in kW or current in A.
3
"5.6.4 Current limitation by current
▪
Allows you to limit the current of the household by limiting the current of
the heat pump system (sum of indoor unit and backup heater).
▪
Limitation of current in A.
4
"5.6.5 BBR16 power
▪
Restriction: Only available in Swedish language.
▪
Allows you to comply with BBR16 regulations (Swedish energy
regulations).
▪
Limitation of power in kW.
▪
Can be combined with the other power consumption controls. If you do
so, the unit uses the most restrictive control.
NOTICE
It is possible to install a field fuse with lower than recommended rating over the heat
pump. For this you must modify field setting [2‑0E] according to the maximum
allowed current over the heat pump.
Note that field setting [2‑0E] overrules all power consumption control settings.
Power limiting the heat pump will reduce performance.
Permanent power limitation is useful to assure a maximum power or current input
of the system. In some countries, legislation limits the maximum power
consumption for space heating and DHW production.
P
i
a
DI
P
Power input
i
t Time
DI Digital input (power limitation level)
a Power limitation active
b Actual power input
Setup and configuration
▪
No additional equipment needed.
Power consumption control
4
limitation" [
46]
sensors" [
4
limitation" [
49]
b
t
4
inputs" [
47]
4
48]
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598592-1A – 2019.12